We build the environment. The customer brings the machines.
ArchitecturePower, liquid and density for accelerators.
Direct-to-chip liquid, closed containment, and a boundary drawn at the rack. What crosses that boundary is contractual, not architectural.
Compute
- POWER
- LIQUID
- RACK
- ACCELERATOR
SpecificationCompute
Stand: 08/2026
IT load, Blankenburg Phase 150 MW IT1
Rack density, campus~50 kW/Rack2
IT load per hall25 MW IT3
Racks per hall504 Racks4
Hall envelope60 × 42 m5
Rack density, Quedlinburg13.6 kW/Rack6
Class, Quedlinburg1–3 MW class7
White space264 m²8
Floor loading600 kg/m²9
Customer hardware boundary, as a written clauseOpen · CTO
02 · ComputeProof
Documents · Capacity brief · not yet published.
Quedlinburg's floors are measured, including their loading. Blankenburg's IT load is a design basis figure and marked as one.
Control
Density is a property of the building. It is fixed before a rack is ordered.
Notes
- 150 MW IT – DESIGN BASIS (DESIGN BASIS) · effective 06/2026 · source: Project data sheet · verified 06.08.2026
- 2~50 kW/Rack – DESIGN BASIS (DESIGN BASIS) · effective 07/2026 · source: Technical concept · verified 13.08.2026
- 325 MW IT – DESIGN BASIS (DESIGN BASIS) · effective 07/2026 · source: Technical concept · verified 13.08.2026
- 4504 Racks – DESIGN BASIS (DESIGN BASIS) · effective 07/2026 · source: Technical concept · verified 13.08.2026
- 560 × 42 m – DESIGN BASIS (DESIGN BASIS) · effective 07/2026 · source: Technical concept · verified 13.08.2026
- 613.6 kW/Rack – DESIGN BASIS (CALCULATED) · effective 07/2026 · source: Cooling calculation · verified 13.08.2026
- 71–3 MW class – DESIGN BASIS (DESIGN BASIS) · effective 08/2026 · source: Project data sheet · verified 06.08.2026
- 8264 m² – DESIGN BASIS (CALCULATED) · effective 08/2026 · source: Technical concept · verified 06.08.2026
- 9600 kg/m² – VERIFIED EXISTING (SIGNED REPORT) · effective 01/2023 · source: Structural drawing · verified 31.07.2026
Document status · Revision 1.0 · Last factual review 13 Aug 2026